Flame Detector Explosion Proof AW-FD702E-IR2 adalah salah satu alat instrumen berupa sensor yang dirancang untuk mendeteksi dan merespon keberadaan nyala api untuk mencegah kebakaran, AW-FD702E-IR2 menggunakan sensor IR yang dirancang khusus, AW-FD702E-IR2 dapat membedakan nyala api lebih efektif antara radiasi nyala api nyata atau nyala api palsu, AW-FD702E-IR2 juga dapat diatur 5 tingkatan sensitivitas sehingga dapat  memenuhi kebutuhan di banyak tempat seperti Industri minyak, Industri gas, Ruang Panel (mesin & listrik), Pabrik, Aula, Gudang.

Fitur dan Kelebihan Flame Detector Explosion Proof AW-FD702E-IR2

  • Konsumsi daya rendah
  • Meliliki chip dengan kinarja terbaik (16-bit)
  • Menggunakan IR Sensor & Solar blind UV Sensor
  • Algortima terbaru, Lebih tepat membaca nyala Api
  • Desain tahan ledakan
  • Biaya perawatan lebih murah,Mudah
  • Sudut deteksi api mencapai 120°

 

Flame Detector Explosion Proof AW-FD702E-IR2

 

Spesifikasi

Item Specification or state
 

Power Suply

Minimum Standart Maximum
18V DC (can be customized 12V DC) 24V DC 30V DC
Working current Monitoring state ≤15Ma, alarm status ≤35mA
Warm-ip time Energized after 60s
Fire alarm When the fire was dicovered monitored, a fire detector into the state

Fire alarm output relay, red fire indicator light.

Fault alarm When they find the sensor, power suply and other abnormalities, the detector enters alarm status.

When the fire alarm and fault occur simultaneously, fire priority.

Alarm threshold 1-5 adjustable (factory set 3).

Monitor the status of each green flashes indicates the alarm threshold.

Alarm delay 0-30S adjustable (factory set to OS).
Drift compensation Sensor hardware compensation and intelegent software

Compensation combined mode.

Can effectively compansate for temperature drift, long-term

Environmental changes and components produced.

Sources of interference suppression Can effectively suppress the influence of non-flame sources of interference, such as sunlight (direct and reflected), commonly used artificial light.

Background radiation, heat moving objects, welding, etc.

Light ·         Monitoring status: green light flashes

·         Fire status: red light

·         Fault status: yellow light

Export ·         Alarm relays, alarm action, the output contacts 1A@ 30VDC 1A@ 250VAC

·         Fault relay, fault action, the output contacts 1A@ 30VDC 1A@ 250VAC

·         Serial communication interface